(regulations 347 to 350, 361, 390 and 391)
Table 11.1
Item | Column 1 Description of hazardous chemical | Column 2 Placard quantity | Column 3 Manifest quantity |
Flammable gases | |||
1 | Flammable gases--category 1A, category 1B or any combination of those categories | 200 L | 5,000 L |
Gases under pressure | |||
2 | Gases under pressure--with acute toxicity, category 1, 2, 3 or 4 | 50 L | 500 L |
3 | Gases under pressure--with skin corrosion, category 1A, 1B or 1C | 50 L | 500 L |
4 | Gases under pressure--not specified elsewhere in this table | 1,000 L | 10,000 L |
Flammable liquids | |||
5 | Flammable liquids--category 1 | 50 L | 500 L |
6 | Flammable liquids--category 2 | 250 L | 2,500 L |
7 | Flammable liquids--category 3 | 1,000 L | 10,000 L |
8 | Flammable liquids--any combination of chemicals from items 5 to 7 where none of the items exceeds the quantities in column 2 or 3 of that item on its own | 1,000 L | 10,000 L |
9 | Flammable liquids--category 4 | 10,000 L | 100,000 L |
Self - reactive substances | |||
10 | Self - reactive substances--type A | 5 kg or 5 L | 50 kg or 50 L |
11 | Self - reactive substances--type B | 50 kg or 50 L | 500 kg or 500 L |
12 | Self - reactive substances--any of types C to F | 250 kg or 250 L | 2,500 kg or 2,500 L |
Flammable solids | |||
13 | Flammable solids--category 1 | 250 kg | 2,500 kg |
14 | Flammable solids--category 2 | 1,000 kg | 10,000 kg |
15 | Flammable solids--any combination of chemicals from items 11 to 14 where none of the items exceeds the quantities in column 2 or 3 of that item on its own | 1,000 kg or 1,000 L | 10,000 kg or 10,000 L |
Pyrophoric liquids and pyrophoric solids | |||
16 | Pyrophoric liquids and pyrophoric solids--category 1 | 50 kg or 50 L | 500 kg or 500 L |
Self - heating substances and mixtures | |||
17 | Self - heating substances and mixtures--category 1 | 250 kg or 250 L | 2,500 kg or 2,500 L |
18 | Self - heating substances and mixtures--category 2 | 1,000 kg or 1,000 L | 10,000 kg or 10,000 L |
19 | Self - heating substances and mixtures--any combination of chemicals from items 16 to 18 where none of the items exceeds the quantities in column 2 or 3 of that item on its own | 1,000 kg or 1,000 L | 10,000 kg or 10,000 L |
Substances which in contact with water emit flammable gas | |||
20 | Substances which in contact with water emit flammable gas--category 1 | 50 kg or 50 L | 500 kg or 500 L |
21 | Substances which in contact with water emit flammable gas--category 2 | 250 kg or 250 L | 2,500 kg or 2,500 L |
22 | Substances which in contact with water emit flammable gas--category 3 | 1,000 kg or 1,000 L | 10,000 kg or 10,000 L |
23 | Substances which in contact with water emit flammable gas--any combination of chemicals from items 20 to 22 where none of the items exceeds the quantities in column 2 or 3 of that item on its own | 1,000 kg or 1,000 L | 10,000 kg or 10,000 L |
Oxidising liquids and oxidising solids | |||
24 | Oxidising liquids and oxidising solids--category 1 | 50 kg or 50 L | 500 kg or 500 L |
25 | Oxidising liquids and oxidising solids--category 2 | 250 kg or 250 L | 2,500 kg or 2,500 L |
26 | Oxidising liquids and oxidising solids--category 3 | 1,000 kg or 1,000 L | 10,000 kg or 10,000 L |
27 | Oxidising liquids and oxidising solids--any combination of chemicals from items 24 to 26 where none of the items exceeds the quantities in column 2 or 3 of that item on its own | 1,000 kg or 1,000 L | 10,000 kg or 10,000 L |
Organic peroxides | |||
28 | Organic peroxides--type A | 5 kg or 5 L | 50 kg or 50 L |
29 | Organic peroxides--type B | 50 kg or 50 L | 500 kg or 500 L |
30 | Organic peroxides--any of types C to F | 250 kg or 250 L | 2,500 kg or 2,500 L |
31 | Organic peroxides--any combination of chemicals from items 29 and 30 where none of the items exceeds the quantities in column 2 or 3 of that item on its own | 250 kg or 250 L | 2,500 kg or 2,500 L |
Acute toxicity | |||
32 | Acute toxicity--category 1 | 50 kg or 50 L | 500 kg or 500 L |
33 | Acute toxicity--category 2 | 250 kg or 250 L | 2,500 kg or 2,500 L |
34 | Acute toxicity--category 3 | 1,000 kg or 1,000 L | 10,000 kg or 10,000 L |
35 | Acute toxicity--any combination of chemicals from items 32 to 34 where none of the items exceeds the quantities in column 2 or 3 of that item on its own | 1,000 kg or 1,000 L | 10,000 kg or 10,000 L |
Skin corrosion | |||
36 | Skin corrosion--category 1A | 50 kg or 50 L | 500 kg or 500 L |
37 | Skin corrosion--category 1B | 250 kg or 250 L | 2,500 kg or 2,500 L |
38 | Skin corrosion--category 1C | 1,000 kg or 1,000 L | 10,000 kg or 10,000 L |
Corrosive to metals | |||
39 | Corrosive to metals--category 1 | 1,000 kg or 1,000 L | 10,000 kg or 10,000 L |
40 | Corrosive to metals--any combination of chemicals from items 36 to 39 where none of the items exceeds the quantities in column 2 or 3 of that item on its own | 1,000 kg or 1,000 L | 10,000 kg or 10,000 L |
Unstable explosives | |||
41 | Unstable explosives | 5 kg or 5 L | 50 kg or 50 L |
Unstable chemicals | |||
42 | Unstable chemicals--any combination of chemicals from items 10, 28 and 41 where none of the items exceeds the quantities in column 2 or 3 of that item on its own | 5 kg or 5 L | 50 kg or 50 L |
Aerosols | |||
43 | Aerosols--category 1, category 2, category 3 or any combination of those categories | 5,000 L | 10,000 L |
Note 1: In item 2, Gases under pressure with acute toxicity, category 4 only applies up to a LC50 of 5,000 ppmV. This is equivalent to dangerous goods of Division 2.3.
Note 2: Item 43 includes flammable aerosols.
1 Determination of classification of flammable liquids
For the purposes of this table, if a flammable liquid category 4 is used, handled or stored in the same spill compound as one or more flammable liquids of categories 1, 2 or 3, the total quantity of flammable liquids categories 1, 2 or 3 must be determined as if the flammable liquid category 4 had the same classification as the flammable liquid in the spill compound with the lowest flash point.
Example: For placarding and manifest purposes, a spill
compound containing 1 000 L of flammable liquid category 1 and 1
000 L of flammable liquid category 4 is considered to contain 2
000 L of flammable liquid category 1