New South Wales Consolidated Regulations

[Index] [Table] [Search] [Search this Regulation] [Notes] [Noteup] [Previous] [Next] [Download] [Help]

STATE ENVIRONMENTAL PLANNING POLICY (EXEMPT AND COMPLYING DEVELOPMENT CODES) 2008 - REG 2.42AB

Development standards

2.42AB Development standards

The standards specified for that development are that the development must--

(a) not have a capacity of more than--
(i) for a fuel tank--5,000 L, or
(ii) for a gas tank--1,000 L, and
(b) be located at least 20m from the primary road frontage of the lot and at least 10m from each other lot boundary, and
(c) be bunded with the capacity to contain at least 110% of the capacity of the tank, and
(d) if a fuel tank--be constructed of prefabricated metal, be freestanding and installed in accordance with the requirements of AS 1940:2017, The storage and handling of flammable and combustible liquids , and
(e) if a gas tank--be designed and constructed in accordance with the requirements of AS/NZS 1596:2014, The storage and handling of LP Gas by a professional engineer, and
(f) not be used for advertising, and
(g) be located at least 1m from any registered easement, sewer main or water main.
Note--: Other existing legislative requirements still apply in relation to work place health and safety issues.



AustLII: Copyright Policy | Disclaimers | Privacy Policy | Feedback